SNAP-SCM-485-422 not recognized after 'Restart I/O unit from powerup' from PAC Manager


Applies To:

SNAP-SCM-485-422

Versions Affected:

Problem was discovered in version: R1.1o
Resolution is included beginning in version: B2.0a


Symptoms:

After issuing the command Tools→Inspect→Status Write→Restart I/O unit from powerup from PAC Manager, a SNAP-PAC brain does not recognize a SNAP-SCM-485-422 module configured for 4-wire mode.

To duplicate the problem:

  1. Use PAC Manager to configure the Mode of Operation for a SNAP-SCM-485-422 to 4-wire mode. Access this area from Tools→Inspect→Communications→Serial Modules. Notice the Module Type shows 0xF1.
  2. Issue the Tools→Inspect→Status Write→Store configuration to flash command.
  3. Issue the Tools→Inspect→Status Write→Restart I/O unit from powerup command.
  4. Check the Module Type. It now shows 0xF3. Notice the 4-wire configuration field is not shown.

Workaround:

Turn the power supply to the rack off and then back on. The Module Type shows 0xF1 again, and the Mode of Operation field correctly shows 4-wire.


Resolution:

Opto 22 has resolved this issue and will include the fix in an upcoming release.


Questions?

Contact: Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com


DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2024 Opto 22. All rights reserved.