KB86186
mistic PID values set from the Debugger Inspect dialog box are overwritten if the scan rate is changed
Revision:  1.0
Published:  2/21/2017
Applies To
SNAP-PAC-S1
SNAP-PAC-S1-FM
SNAP-PAC-S1-W
SNAP-PAC-S2
SNAP-PAC-S2-W
Versions
Versions affected:  
All PAC firmware versions through R9.5d

SYMPTOMS

Note: This issue applies only when using PAC Control Professional with Legacy strategy options enabled (File > Strategy Options > Legacy tab).

In PAC Control Professional Debug mode, if you use the Inspect dialog box to change mistic PID values, and later, you use the Edit PID Loop dialog box to change the scan rate for the same mistic PID, the controller incorrectly resets all mistic PID parameters to the values configured in the PAC Control strategy, which may or may not be the current values.

WORKAROUND

  1. If possible, set the scan rate first.
    or
  2. Store the new PID parameter values in strategy logic.
    When you want to change the scan rate, first set the desired scan rate, and then use strategy logic to set all other PID parameters to the values saved in the strategy.

RESOLUTION

Opto 22 has resolved this issue and will include the fix in an upcoming release.

Relevant Downloads
No relevant downloads have been specified.
Questions? Contact Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com

DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2017 Opto 22. All rights reserved.

My.Opto22

All Opto22

Request Information
  • FREE Product Brochure
  • Product Demonstration
  • PreSales Engineering Assistance

Opto 22 Product Support

Opto 22 Product Support is FREE Monday through Friday 7 a.m. to 5 p.m. Pacific Time

Product Support Numbers:

Local: (951) 695-3080
Toll-Free: (800) 835-6786
Fax: (951) 695-3017
support@opto22.com

Products

None

Downloads

None

Documents

None