PAC Manager: Updating to newer firmware may fail in R1, R1-B, and R2 controllers with microSD card slot
Revision:  3.0
Published:  9/27/2016
Applies To
PAC Manager when installing firmware on these controllers:
SNAP-PAC-R1 with microSD card slot
SNAP-PAC-R1-FM with microSD card slot
SNAP-PAC-R1-B with microSD card slot
SNAP-PAC-R2 with microSD card slot
SNAP-PAC-R2-FM with microSD card slot
Versions
Versions affected:  
PAC Manager R9.3a through R9.5a
Problem is fixed in version:  
PAC Manager R9.5b

SYMPTOMS

Updating firmware on R-series controllers with microSD card slots may fail if the newer firmware file is too large to install on the controller using the normal update process (Tools > Maintenance > Install Firmware).

Note that this issue does not affect:

  • Wireless controllers.
  • Controllers that do not have microSD card slots.
If the firmware update fails, PAC Manager may display a "Firmware update completed, but restart could not be confirmed" message, and in Tools > Inspect, you may notice that bridge firmware S9.2c is installed on the controller.

NOTE

This issue can also occur when the controller is programmed with a private key as a part of Secure Strategy Distribution (using PAC Terminal SSD).

To determine if your controller is configured for SSD, use PAC Manager's Inspect mode (Tools > Inspect).
Select "Other," and then set:

  • The Address field to F408004
  • The Type to 32-Bit Integer
  • The Length to 1

Then click Refresh.

If the value is 2, then the controller is configured for SSD. For instructions to update the firmware in your controller, see the PAC Terminal SSD documentation.

WORKAROUND

The best workaround is to upgrade to PAC Manager R9.5b or higher.
If that's not possible, follow these steps to work around the issue:

  1. If a secondary IP address is configured, write down the current parameters (you'll need them in Step 5), and then use PAC Manager's Status Write page (Tools > Inspect, Status Write button, ETHERNET 2 Interface area) to set the configuration back to 0.0.0.0 in all fields.  Be sure to click the Apply button.
  2. On the Status Write page, select "Reset to defaults and Restart Device" and then click the Send Command button.
  3. Make sure PAC Manager R9.5a or higher is installed, and then use it to install firmware R9.5a.
  4. Install the desired firmware version (R9.5b or higher).
  5. Use the Status Write page to configure the ETHERNET 2 interface again.

RESOLUTION

Opto 22 has resolved this issue.

Relevant Downloads
No relevant downloads have been specified.
Questions? Contact Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com

DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2017 Opto 22. All rights reserved.

My.Opto22

All Opto22

Request Information
  • FREE Product Brochure
  • Product Demonstration
  • PreSales Engineering Assistance

Opto 22 Product Support

Opto 22 Product Support is FREE Monday through Friday 7 a.m. to 5 p.m. Pacific Time

Product Support Numbers:

Local: (951) 695-3080
Toll-Free: (800) 835-6786
Fax: (951) 695-3017
support@opto22.com

Products

None

Downloads

None

Documents

None