PAC Control: Using custom scaling with analog points on mistic I/O units causes error
Revision:  3.0
Published:  3/31/2016
Applies To
PAC Control Basic
PAC Control Professional
Versions
Problem affects versions:  
R9.4b and higher
Problem is fixed in version:  
R9.5a

SYMPTOMS

When you run your PAC Control strategy, the controller configures the I/O units and points. If you use scaling on a mistic I/O point, communication to the I/O unit may become disabled, or the I/O values may be very inaccurate. This issue is due to a change in point scaling as of PAC Control R9.4b.

You will see the mistic I/O unit return an error. The controller will detect the error and disable communications.

WORKAROUND

When working with mistic I/O units, you can get around this issue by using PAC Control 9.4a or lower.
HOWEVER, by the time you see the issue, you will have opened your strategy in PAC Control R9.4b or higher, which introduced the issue into your strategy. In that case, the workaround is to:

  1. Find an archived version of your strategy—one that hasn't been opened in PAC Control R9.4b or higher.
  2. Uninstall PAC Control.
  3. Download and install PAC Control R9.4a.
  4. Open and save the archived version of your strategy.

RESOLUTION

Opto 22 has resolved this issue.

Relevant Downloads
No relevant downloads have been specified.
Questions? Contact Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com

DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2017 Opto 22. All rights reserved.

My.Opto22

All Opto22

Request Information
  • FREE Product Brochure
  • Product Demonstration
  • PreSales Engineering Assistance

Opto 22 Product Support

Opto 22 Product Support is FREE Monday through Friday 7 a.m. to 5 p.m. Pacific Time

Product Support Numbers:

Local: (951) 695-3080
Toll-Free: (800) 835-6786
Fax: (951) 695-3017
support@opto22.com

Products

None

Downloads

None

Documents

None