KB50250
Published: July 8, 2008
Revision: 1.0

Problems with the OptoControl AB Integration Kit


Applies To:

Allen-Bradley DF1 Integration Kit for OptoControl

Versions Affected:

Problem was discovered in version: R3.0
Problem is fixed in version: R4.0

Resolved In Version:

Problem is fixed in version: R4.0


Symptoms:

Reading binary files fails when using the AB Typed Read subroutine. There is a missing connection from block 613 to block 614.

Error -60 is added each time subroutines AB Protected Typed Logical Read and AB Protected Typed Logical Write are called (such as from the AB SLC Master example strategy). Pointer table AB_MASTER_POINTER_TABLE is incorrectly initialized in block 262 of the Powerup chart. The ASCII_DATA string table should be moved to AB_MASTER_POINTER_TABLE[2], but instead AB_MASTER_INTEGER_TABLE was moved to that pointer table element.


Resolution:

Opto 22 has resolved these issues.


Questions?

Contact: Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com


DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2024 Opto 22. All rights reserved.